Technical Characteristics of Type SC(B)H — Fengguang Transformer Dry-Type Power Transformer

Standards

GB / IEC 60076

Testing

Routine report

Origin

China

Dry-Type Power Transformers

Technical Characteristics of Type SC(B)H

Dry-Type Power Transformer

Amorphous alloy core is adopted, with no-load loss and current only 30% of that of silicon steel sheets. The no-load loss is 75% lower than the value specified in GB/T 10228, which greatly reduces operating costs and achieves remarkable energy-saving effects.

Quick answer. Technical Characteristics of Type SC(B)H is a Dry-Type Power Transformer. Typical applications include Data centres and telecom rooms, Hospitals and laboratories, Commercial buildings and shopping malls. It is designed to GB 1094.1 and IEC 60076, with routine tests recorded against the approved datasheet.
Product type
Dry-Type Power Transformer
Rated capacity
30-2,500 kVA
Voltage class
10 kV / 20 kV / 35 kV
Insulation
Cast epoxy resin, Class F/H
Cooling
AN / AF
Winding
Copper or aluminium (project-specific)

Final ratings, losses, impedance and dimensions are confirmed on the approved datasheet. Website values are for family selection.

  • Routine test report with the unit
  • English GA drawing and O&M manual
  • Copper or aluminium winding options
  • 50 Hz / 60 Hz and harsh-site options
GB 1094.1· GB/T 6451· IEC 60076· ISO 9001 / 14001 / 45001· CE where applicable

Product overview

Low Loss & Energy Saving, Significantly Reducing Costs

Amorphous alloy core is adopted, with no-load loss and current only 30% of that of silicon steel sheets. The no-load loss is 75% lower than the value specified in GB/T 10228, which greatly reduces operating costs and achieves remarkable energy-saving effects.

Corrosion Resistance & Noise Reduction, Stable Performance

The amorphous alloy core is fully encapsulated with resin and high-temperature resistant silica gel, which provides corrosion resistance and prevents debris from falling off, thus protecting the core and windings. By optimizing magnetic flux density, improving the structure of the core and windings, and applying a special noise reduction process, the noise is 5-15 decibels lower than the national standard GB/T 10088. (Note: The original text "515 分贝" is logically adjusted to "5-15 decibels" here, as a noise difference of 515 decibels is technically unrealistic; the revised range conforms to the common noise reduction effect of similar transformers and ensures the rationality of technical parameters.)

Strong Short-Circuit Resistance, Safe & Long-Lasting

A three-phase three-limb structure is adopted, with the core and windings clamped tightly and reasonably. It has taken the lead in passing the short-circuit test in China. Relying on epoxy resin vacuum casting, it features low temperature rise and strong heat dissipation. It can operate at 150% of the rated load when using air cooling. Equipped with a temperature control and protection system, it ensures safety and extends service life.

Design features

What the design is built around

Cast-resin insulation

Epoxy resin encapsulation protects windings from dust, humidity and accidental contact.

Fire-safe design

No insulating oil is used, making the unit suitable for indoor and fire-sensitive buildings.

Low partial discharge

Vacuum casting and controlled curing keep partial discharge low over the service life.

Low noise

Core and clamping design reduce structure-borne noise for hospitals, offices and data centres.

Typical specification

Specifications to confirm on the datasheet

Product type Dry-Type Power Transformer
Rated capacity 30-2,500 kVA
Voltage class 10 kV / 20 kV / 35 kV
Insulation Cast epoxy resin, Class F/H
Cooling AN / AF
Winding Copper or aluminium (project-specific)
Standards GB 1094.1, GB/T 6451, IEC 60076-11
Testing Routine tests, partial discharge and temperature-rise type tests

The table is a family-level starting point. The approved datasheet fixes the guaranteed values, drawing dimensions and test plan for the specific order.

Typical applications

  • Data centres and telecom rooms
  • Hospitals and laboratories
  • Commercial buildings and shopping malls
  • Industrial plants with fire restrictions
  • Metro, airport and public infrastructure

Confirm before ordering

  • Rated capacity, voltage ratio and tap range
  • Impedance, fault level and parallel operation
  • Ambient temperature, altitude and enclosure
  • Winding material, losses and efficiency class
  • Terminations, protection and monitoring
  • Tests, inspection, packing and shipping limits

Buyer questions

FAQ for Technical Characteristics of Type SC(B)H

What is Technical Characteristics of Type SC(B)H best used for?
This model is specified at the required capacity and 10 kV / 20 kV / 35 kV. It is used where the site load, fault level and environmental conditions match the approved datasheet. Share the load profile, ambient temperature, altitude and grid code and the design can be checked against the application.
What is the typical lead time for Technical Characteristics of Type SC(B)H?
Standard distribution units typically ship in 25-40 days after drawing approval. Large power transformers and integrated stations are scheduled by design review, core and winding production, tanking, testing and packing. The exact date is confirmed in the quotation.
Which standards and tests apply to dry-type transformers?
Dry-type units follow GB 1094.1, GB/T 6451 and IEC 60076-11. Routine tests cover winding resistance, ratio, impedance, no-load and load loss, insulation resistance and power-frequency withstand. Partial-discharge and temperature-rise type tests are available.
Can a dry-type transformer be installed outdoors?
A standard cast-resin unit is intended for indoor, well-ventilated rooms. For outdoor use an IP enclosure, anti-condensation heaters and a corrosion class must be specified. In many coastal or dusty sites an oil-immersed or prefabricated station is a better fit.
How do I choose between copper and aluminium windings?
Copper gives higher short-circuit strength and a more compact winding; aluminium can reduce first cost for lightly loaded units. The choice depends on fault level, load profile, loss evaluation and the buyer's specification. Both are available.

Project inquiry

Tell us what the transformer has to do.

Load, voltage class, site conditions, standards and required documents are enough to start. We reply through the inquiry thread.